Connecting -48V DC Power Supply Modules

The GigaVUE‑HC1-Plus is available with DC power supply modules. This section provides instructions for connecting a -48V DC power source to the DC power supply modules.

To connect a -48V DC input to the DC power supply module:

1.   Plug the DC power cable adapter into the DC power supply.

Note:  Terminal block supports 10AWG.

2. If PSM grounding is required, connect earth ground to the SAFETY GROUND (green/yellow) terminal using a straight blade screwdriver.

Note:  An adapter or pigtail, both of which are in the shipping package, is required for the PWR-TAC22 DC/DC PSU.

Note:  Pigtails or adapters are not required for the PWR-HC1P2 DC/DC PSU.

1 Connecting DC Power Supply Module (2 different type of power modules)
3. Connect the positive and negative power wires to the appropriate terminals using a straight blade screwdriver.
o   Connect positive source wire to the + RETURN (black) terminal using a straight blade screwdriver.
o   Connect -48V source wire to the -48V (blue) terminal using a straight blade screwdriver.

Important: The leads to the DC power supply modules on the GigaVUE‑HC1-Plus node should attach from the side of the chassis away from the terminal block. Run the wires to avoid obstructing airflow for the adjacent fans.