Connecting -48V DC Power Supplies
The GigaVUE Traffic Aggregator is available with two DC power supplies instead of the standard AC power supply. This section provides instructions for connecting a -48V DC power source to the DC power supplies.
To connect a -48V DC input to the DC power supply:
|
Figure 18
|
Connecting -48V DC Power Cable Adapter |
|
1.
|
Plug the DC power cable adapter into the DC power supply. |
Note: Terminal block supports 10AWG.
|
2.
|
If PSM grounding is required, connect earth ground to the SAFETY GROUND (green/yellow) terminal using a straight blade screwdriver. |
|
3.
|
Connect the positive and negative power wires to the appropriate terminals using a straight blade screwdriver. |
|
•
|
Connect the positive source wire to the + RETURN (black) terminal using a straight blade screwdriver. |
|
•
|
Connect the -48V source wire to the -48V (blue) terminal using a straight blade screwdriver. |
Important: The leads to the DC power supply modules on the GigaVUE-TA Series node should attach from the side of the chassis away from the terminal block. Run the wires to avoid obstructing airflow for the adjacent fans.
|
4.
|
Repeat Step 1 through Step 3 for the other power supply modules. |